Eaton's MPN:
ESF631-TN-E
1 Phase, 63A, 100kA, Imax L-N, plus 50kA Imax N-E, enclosed
Compact solution for Class II / Cat B, C & D, Point of Entry, distribution board and sub board surge protection
All mode protection L-N, L-E & N-E
High kA rating per phase 100kA, Imax
Exceptionally low let through voltage <600V @ 3kA/8/20us, <800V @ 50kA / 8/20us, Inom
50A to 80A single and three phase models
Fully enclosed and gear tray versions to suit switch boards
Can be configured for 3:1 phase bypass loads
Available in TN & TT systems versions
5 Year Warranty
Technical Specifications
Specifications
|
Battery
|
|
Communication/Management
|
|
Frequency
|
|
Input Connection
|
|
Input Voltage
|
220 – 250VAC
|
Misc.
|
|
Output Receptacles
|
|
Output Voltage
|
|
Power Rating/Capacity
|
|
Series
|
|
Typical Runtime
|
|
Warranty
|
5 Years
|
x`
|
|
Alarms/indicators
|
|
Current rating - continuous
|
50, 63 or 80A
|
In 8/20us (Neutral-Earth)
|
50kA
|
Ismax 8/20us ( Line Neutral )
|
100kA
|
Nominal surge lifetime
|
15 hits @ 50kA (8/20uS, each mode)
|
Primary protection modes
|
Line-Neutral, Neutral-Earth
|
Service type
|
TN-S, TN C-S SYSTEMS
|
Short circuit withstand (1 sec)
|
29kA
|
Terminations
|
Bolted lug. 8mm bolts for phase and neutral connections. 6mm PE (earth) stud provided on gear tray. All connections identified on unit.
|
Specifiications
|
Recommended maximum over current protection
|
HRC gL fuse rated according to the unit’s rating
|